HomeMy WebLinkAbout2560410 - Report Received from Internal Staff - Fire
Monaghan Fire & Civil Protection
Monaghan Fire Station
Annahagh
Monaghan
Co. Monaghan
28/10/2025
Planning Section,
Monaghan County Council,
The Glen,
Monaghan
Planning App. Ref. No. 25/60410
Applicant Retention of internal alterations to previous approved plans
under 20/155 including the following: 1. Conversion of attic of
528.41sq.m. floor area for the provision of 9 no. bedrooms,
associated stairs and lift core. 2. Alterations to previously
approved layout of ground floor in relation to 11 no.
bedrooms, storage and staircase locations. 3. Alterations to
previously approved layout on first floor in relation to
bedroom, storage and staircase locations. 4. Repurposing of
existing ground floor meeting room (62.00sq.m.) to additional
kitchen and laundry facilities. 5. All associated site
development work
No objections to the Planning Application subject to the following conditions:
1. The proposed development shall obtain a flre safety certiflcate in accordance with S.I. No.
305/1991 – Building Control Regulations, 1991, prior to construction.
2. Any buildings work to be retained shall obtain a Regularisation Fire Safety Certiflcate in
accordance with S.I. No. 351/2009 Building Control (Amendment) Regulations, 2009.
3. The proposed works shall be designed and constructed in accordance with the requirements of
Part B Fire Safety 2006, of the Second Schedule of the Building Regulations, 1997-2019.
4. Fire Hydrants shall be in accordance with BS 750:2012 and shall deliver a minimum rate of fiow
as per Monaghan Fire & Civil Protection ‘Guidance document for flre-flghting water supplies’.
5. Fire Hydrants shall be in accordance with BS 750:2012 and shall deliver a minimum rate of fiow
of 25 l/sec sustainable for 120 minutes in conjunction with peak daily demand.
6. Fire Brigade Vehicle access shall be provided in accordance with Clause 5.2 of Technical
Guidance Document Part B Fire Safety 2006 including turning facilities where dead-ends
exceed 20.0m.
7. The proposed works shall be designed and constructed in accordance with Part M Access &
Use, of the Second Schedule of the Building Regulations, 1997-2019.
8. The proposed works shall obtain a Disability Access Certiflcate in accordance with S.I. No.
351/2009 - Building Control (Amendment) Regulations 2009, prior to construction.
Regards
Dermot Brannigan
Chief Fire Officer