HomeMy WebLinkAbout2560451 - Other Assessments CMD ARCHITECTS LTD CLIENT: SRAGH CAR DISMANTLERS PROPOSED DEVELOPMENT AT SRAGH, BALLYBAY CO.MONAGHAN DETAILS OF STORMWATER ATTENUATION SYSTEM RECEIVED: 12/11/2025 Introduction The stormwater attenuation system design has been prepared on the basis of minimizing the effect of the development by comparison with the expected storm runoff for the site as an undeveloped green-field site. Basis for Design The attenuation system has been designed on the basis of 24 hour average rainfall for a 30 year return period. The extreme rainfall return periods for the site location were obtained from Met Eireann and the 24 hour rainfall for a 30 year period was calculated by averaging figures to be 70mm. The volumes of stormwater runoff were calculated on the basis of recognized runoff coefficients for the various surfaces types on the site. The following formula was used to calculate stormwater runoff; Runoff (m3/day) = Area (m2) x Rainfall (mm/day) x Runoff Coefficient The additional storm runoff per day due to the site development was used to calculate the size of the storage tank and the flow control system has been sized to deliver water to the drainage system at a flow rate equivalent to the undeveloped site. A high level emergency overflow has been provided for use in the event of storm conditions in excess of the 30 year return. This design was also checked for attenuation of a 30 minute storm with a 10 year return period in accordance with BRE Digest 365. RECEIVED: 12/11/2025 System Design Undeveloped Site Site Area = 27740.86m2 Estimated Average Rainfall over 24 hours for 30 year return period = 70mm Grassland Area Runoff Coefficient = 0.2 Runoff from Undeveloped Site = 27740.86m2 x 0.07 x 0.2 = 388.37m3/day Peak flow rate based on 35mm/hour = 27740.86m2 x 0.035 x 0.2 = 194m³/hour Developed Site Roofs, Concrete & Tarmac Areas Area = Roof = 1322.67 m2 & 1245.60m2 Existing yard area. + Proposed yard area 497.50m2. Hardstand Runoff Coefficient =1.0 Runoff = 3065.77 x 0.07 x 1.0 = 214.60m3/day Gravel Area Area = 7959.77m2 Runoff Coefficient = 0.8 Runoff = 7959.77x 0.07 x 0.2 = 111.40m3/day Landscaping Areas Area= 0m2 Runoff Coefficient = 0.2 Runoff = 0 x 0.07 x 0.2 = 0m3/day Total Runoff from Developed Site = 326.0m3/day Additional Runoff Due to Site Development = Total Runoff from Developed Site - Runoff from Undeveloped Site Additional Runoff Due to Site Development = 326.0 – 194 = 132 m3/day Add 20% for Climate Change = 132 x1.2 = 158m 3/day Required Attenuation Tank Capacity = 158m3 Reinforced Concrete Attenuation Tank Dimensions = 14m x 4.8m x 2.40m Deep = 161.28m3 (Extra capacity allowance for internal wall and water level 150mm below top of wall) Outflow Regulator = 214.60m3/day / 24 = 8.94m3/hr Design Petrol Interceptor Nominal Flow = 27.75m3/day = 27750litres /12hours / 60minutes / 60seconds = 0.3 l/s Peak Flow = for 30 minute storm, 10 year return = 16.9 l/s Use JFC Full Retention Petrol Interceptor or similar approved Model: BPDA2500 Nominal Flow: 4.5 l/s Peak Flow: 45 l/s Oil Storage: 67.5 litres Outflow Hydrobreak Use JFC Hydro-Valve Vortex Flow Control in 1200mm Diameter Precast Manhole RECEIVED: 12/11/2025 Met Eireann Return Period Rainfall Depths for sliding Durations Irish Grid: Easting: 274304, Northing: 317450, Interval | YearsDURATION 6months, 1year, | 2, 3, 4, 5, 10, 20, 30, 50, 75, 100, 120, 5 mins 3.0, 4.1, | 4.7, 5.6, 6.2, 6.7, 8.2, 9.8, 10.9, 12.4, 13.7, 14.7, 15.4, 10 mins 4.2, 5.8, | 6.6, 7.8, 8.7, 9.3, 11.4, 13.7, 15.2, 17.3, 19.1, 20.5, 21.5, 15 mins 4.9, 6.8, | 7.8, 9.2, 10.2, 10.9, 13.4, 16.1, 17.8, 20.3, 22.5, 24.2, 25.3, 30 mins 6.5, 8.9, | 10.1, 11.9, 13.1, 14.0, 16.9, 20.2, 22.4, 25.3, 27.9, 29.9, 31.2, 1 hours 8.6, 11.6, | 13.1, 15.3, 16.8, 17.9, 21.5, 25.4, 28.0, 31.5, 34.6, 36.9, 38.5, 2 hours 11.4, 15.1, | 16.9, 19.7, 21.5, 22.9, 27.2, 32.0, 35.0, 39.2, 42.9, 45.7, 47.5, 3 hours 13.4, 17.6, | 19.7, 22.8, 24.8, 26.4, 31.3, 36.6, 40.0, 44.6, 48.7, 51.7, 53.8, 4 hours 15.1, 19.7, | 22.0, 25.3, 27.5, 29.2, 34.5, 40.2, 43.9, 48.9, 53.2, 56.5, 58.7, 6 hours 17.8, 23.0, | 25.6, 29.4, 31.9, 33.7, 39.6, 46.0, 50.1, 55.6, 60.3, 63.9, 66.3, 9 hours 20.9, 26.8, | 29.8, 34.1, 36.8, 38.9, 45.5, 52.6, 57.1, 63.2, 68.4, 72.4, 75.0,12 hours 23.5, 29.9, | 33.2, 37.8, 40.8, 43.1, 50.3, 57.9, 62.7, 69.2, 74.8, 79.0, 81.8,18 hours 27.6, 35.0, | 38.6, 43.9, 47.2, 49.8, 57.7, 66.2, 71.5, 78.7, 84.9, 89.5, 92.6,24 hours 31.0, 39.0, | 43.0, 48.7, 52.4, 55.1, 63.7, 72.8, 78.5, 86.2, 92.8, 97.7, 101.0, 2 days 38.8, 47.9, | 52.4, 58.7, 62.7, 65.7, 75.0, 84.7, 90.7, 98.8, 105.7, 110.9, 114.2, 3 days 45.6, 55.6, | 60.4, 67.2, 71.6, 74.8, 84.8, 95.1, 101.5, 110.1, 117.3, 122.7, 126.2, 4 days 51.6, 62.5, | 67.7, 75.0, 79.6, 83.1, 93.7, 104.6, 111.4, 120.3, 127.9, 133.5, 137.2, 6 days 62.7, 75.0, | 80.9, 89.1, 94.2, 98.0, 109.7, 121.7, 129.1, 138.8, 147.0, 153.0, 157.0, 8 days 72.9, 86.5, | 92.9, 101.8, 107.5, 111.6, 124.3, 137.2, 145.1, 155.5, 164.2, 170.7, 174.9, 10 days 82.5, 97.2, | 104.2, 113.8, 119.9, 124.3, 137.9, 151.6, 160.0, 171.1, 180.3, 187.1, 191.6, 12 days 91.7, 107.5, | 115.0, 125.2, 131.6, 136.4, 150.7, 165.3, 174.2, 185.8, 195.5, 202.6, 207.3, 16 days 109.3, 127.0, | 135.4, 146.8, 153.9, 159.2, 175.0, 191.0, 200.7, 213.4, 224.0, 231.7, 236.8, 20 days 126.0, 145.6, | 154.8, 167.3, 175.0, 180.8, 198.0, 215.2, 225.7, 239.3, 250.7, 259.0, 264.4, 25 days 146.3, 168.0, | 178.1, 191.8, 200.3, 206.5, 225.3, 244.0, 255.3, 270.1, 282.3, 291.2, 297.0, NOTES:These values are derived from a Depth Duration Frequency (DDF) Model update 2023For details refer to:’Mateus C., and Coonan, B. 2023. Estimation of point rainfall frequencies in Ireland. Technical Note No. 68. Met Eireann’, Available for download at: http://hdl.handle.net/2262/102417RECEIVED: 12/11/2025 Greenfield runoff rate estimation tool www.uksuds.com | Greenfield runoff rate estimation tool (https://www.uksuds.com/) This is an estimation of the greenfield runoff rates that are used to meet normal best practice criteria in line with Environment Agency guidance “Rainfall runoff management for developments”, SC030219 (2013), the SuDS Manual C753 (CIRIA, 2015) and the non-statutory standards for SuDS (Defra, 2015). This information on greenfield runoff rates may be the basis for setting consents for the drainage of surface water runoff from sites. Project details Date Calculated by Reference Model version Location Site name Site location Site easting (Irish Grid) Site northing (Irish Grid) Site easting (Irish Transverse Mercator) Site northing (Irish Transverse Mercator) Site details Total site area (ha) + – © OpenStreetMap (https://www.openstreetmap.org/copyright) contributors. ha 29/10/2025 Owen Cunningham Sragh Dismantlers 2.2.1 sragh dismantlers sragh Ballybay co.monaghan 274313 317455 674248 817464 2.77 We use cookies on this site to enhance your user experience By clicking the Accept button, you agree to us doing so. OK, I AGREE MORE INFORECEIVED: 12/11/2025 Greenfield runoff Method Method IH124 My value Map value SAAR (mm)1000 How should SPR be derived? WRAP soil type 2 SPR QBar (IH124) (l/s) Growth curve factors My value Map value Hydrological region 13 1 year growth factor 2 year growth factor 10 year growth factor 30 year growth factor 100 year growth factor 200 year growth factor IH124 mm WRAP soil type 2 l/s 13 1000 0.3 7.7 0.85 0.95 1.4 1.65 1.95 2.15 We use cookies on this site to enhance your user experience By clicking the Accept button, you agree to us doing so. RECEIVED: 12/11/2025 Results Method Flow rate 1 year (l/s) Flow rate 2 year (l/s) Flow rate 10 years (l/s) Flow rate 30 years (l/s) Flow rate 100 years (l/s) Flow rate 200 years (l/s) Please note runoff estimation is subject to significant uncertainty. Results are therefore normally reported to only 1 decimal place. Where 2 decimal places are provided, this does not indicate accuracy to this level, it has been adopted to prevent ‘zero’ figures from being reported. Outputs less than 0.01 l/s are reported as 0.01 l/s. Disclaimer This report was produced using the Greenfield runoff rate estimation tool (2.2.1) developed by HR Wallingford and available at uksuds.com (https://www.uksuds.com/). The use of this tool is subject to the UK SuDS terms and conditions and licence agreement, which can both be found at uksuds.com/terms-conditions (https://www.uksuds.com/terms-conditions). The outputs from this tool have been used to estimate Greenfield runoff rates. The use of these results is the responsibility of the users of this tool. No liability will be accepted by HR Wallingford, the Environment Agency, Centre for Ecology and Hydrology, Wallingford Hydrosolutions or any other organisation for the use of these data in the design or operational characteristics of any drainage scheme. l/s l/s l/s l/s l/s l/s IH124 6.5 7.3 10.7 12.6 14.9 16.5 We use cookies on this site to enhance your user experience By clicking the Accept button, you agree to us doing so. RECEIVED: 12/11/2025 RECEIVED: 12/11/2025 Dims (mm) Min. Chamber Diameter 1200 Min. Outlet Pipe Diameter 100 Min. Sump Depth 200 FPM-SB1-02000-00200-0100 Head (m)Flow (l/s) Design Point 2.00 2.00 Flush Flow 0.21 1.49 Kick Back 0.52 1.10 Contractor: Site: Date: n/a Sragh 29/10/2025 Chamber Ref: LUGS (Default)Mounting Style:Created By:peter clarke Head(m):2 Flow(l/s):2 Head (m)Flow (l/s) 0 0.00 0.08 1.08 0.17 1.44 0.25 1.49 0.33 1.46 0.41 1.37 0.5 1.17 0.58 1.16 0.66 1.23 0.74 1.30 0.83 1.37 0.91 1.43 0.99 1.48 1.07 1.54 1.16 1.59 1.24 1.64 1.32 1.68 1.4 1.73 1.49 1.77 1.57 1.81 1.65 1.85 1.74 1.89 1.82 1.92 1.9 1.96 1.98 1.99 2.07 2.03 2.15 2.06 2.23 2.09 2.31 2.12 2.4 2.15 Knockloughrim Precast Office: T. 028 79549026 The unique performance characteristics of this StormBrakeŒare derived from extensive dynamic modelling using parametric experimental testing and computational fluid dynamics. Ellistown Precast Office: T. 01530 240000 Email: info@fpmccann.co.uk Web: www.fpmccann.co.uk Device Ref:RECEIVED: 12/11/2025 INSTALLATION INSTRUCTIONS 1. Position the StormBrakeŒso that the inlet is at the bottom and the device outlet is in line with the chamber outlet pipe. 2. Mark the locations of the mounting points on the chamber/mounting wall. 3. Using the marked locations, drill holes to the required thickness and depth for the supplied masonry anchors (M10 throughbolts require 11 mm holes). Fit the bolts to the holes. 4. Attach the StormBrakeŒto the anchor points, ensuring the neoprene gasket is flush with the chamber wall, and fasten the device by tightening the bolts. This will compress the neoprene gasket to provide a watertight seal between the StormBrakeŒand the wall. 5. Fix the stainless steel wire cable from the front bypass door to the underside of the manhole cover, vertically above the device. A secondary bracket is supplied and should be fitted halfway up the chamber to guide the bypass door cable to the top. 6. Adjust the length of the bypass door cable accordingly, so that it reaches the ground level whilst ensuring the bypass door can open if required. Ensure the bypass door is closed for normal operating conditions. Geometry Annotation (mm) Device Vortex Diameter Dv 299 Device Width Dw 66 Device Orifice Do 60 Sump Depth (outlet Ø100mm)Sd 200 Mounting Block Width Mw 540 Mounting Block Height Mh 580 Dimensions quoted are minimum values based on the geometry of this unique StormBrakeŒ unit. These ensure the device can be fitted to the flow control chamber without restriction and meet the performance specification.RECEIVED: 12/11/2025 ATK 010-030GV ATK 040-050GV ATK 060GV ATK 070-100GV Part Material Remarks 1 FRAME PLATE HDPE 2 VALVE DOOR HDPE 3 REINFORCEMENT RIBS HDPE 4 HINGE AISI 316 5 HINGE PIN HDPE 6 HINGE COVER AISI 316 7 SEALING EPDM 8 LIFTING EYE A4 9 BALLAST AISI 316 ATK 010-060GV Steel in HDPE ATK 070-100GV 10 SEALING Neoprene Modifications reserved. HDPE FLAP VALVE ATK-GV with passage ø100-1000mmRECEIVED: 12/11/2025 12/02/2018 ATK 110-150GV Part Material Remarks 1 FRAME PLATE HDPE 2 VALVE DOOR HDPE 3 REINFORCEMENT RIBS HDPE 4 HINGE AISI 316 5 HINGE PIN HDPE 6 HINGE COVER AISI 316 7 SEALING EPDM 8 LIFTING EYE A4 10 SEALING Neoprene 11 REINFORCEMENT PROFILE AISI 316 Modifications reserved. HDPE FLAP VALVE ATK-GV with passage ø1100-1500mmRECEIVED: 12/11/2025 front view side view Diameter ø100 ø150 ø200 ø250 ø300 X 190 240 280 330 395 K 95 120 140 165 197 L 175 200 225 250 275 Y 270 320 365 415 472 DO 237 288 333 391 432 DC 104 131 135 143 163 OA 63°64°66°67°68° number of chem. anchors 4xM10 4xM10 4xM10 4xM10 4xM10 weight in kg 5 6 7 8 10 HDPE FLAP VALVE ATK-GV with passage ø150-300mmRECEIVED: 12/11/2025 front view side view Diameter ø400 ø500 X 480 580 K 240 290 L 335 370 Y 575 660 DO 532 624 DC 140 140 OA 71°72° number of chem. anchors 4xM10 4xM10 weight in kg 15 20 HDPE FLAP VALVE ATK-GV with passage ø400-500mmRECEIVED: 12/11/2025 front view side view Diameter ø600 X 900 K 450 L 500 Y 950 DO 725 DC 160 OA 73° number of chem. anchors 16xM10 weight in kg 33 HDPE FLAP VALVE ATK-GV with passage ø600mmRECEIVED: 12/11/2025 front view side view Diameter ø700 ø800 ø900 ø1000 X 1000 1100 1140 1240 K 500 550 585 635 L 550 600 635 685 Y 1050 1150 1220 1320 DO 825 925 1022 1127 DC 180 200 235 260 OA 74°75°75°76° number of chem. anchors 16xM10 16xM10 20xM10 24xM10 weight in kg 42 55 62 74 HDPE FLAP VALVE ATK-GV with passage ø700-1000mmRECEIVED: 12/11/2025 12/02/2018 front view side view Diameter ø1100 ø1200 ø1300 ø1400 ø1500 X 1400 1500 1600 1700 1800 K 675 750 800 850 900 L 805 845 875 925 975 Y 1480 1595 1675 1775 1875 DO 1311 1348 1507 1603 1709 DC 227 227 247 247 247 OA 76°76°76°76°76° number of chem. anchors 30xM10 30xM10 32xM10 34xM10 36xM10 weight in kg 76 80 95 125 140 HDPE FLAP VALVE ATK-GV with passage ø1100-1500mmRECEIVED: 12/11/2025 European Communities (Shipments of Hazardous Waste Exclusively within Ireland) Regulations 2011 Waste Transfer Form (WTF) for shipments of hazardous waste transported within the State (NOT to be used for shipment into or out of the State) WTF Notifier Details W TF Number: MN190825004 W TF Status: ACTIVE Notifier Name: Enva Ireland Limited (W 0192-03) Notifier Address: 402 Greenogue Business Park, Rathcoole Type of Collection: Single Collection Date Shipped: 23/10/2025 Tonnes Shipped: 3 Volume Shipped (m3): Reference: WCP Details W CP Holder: Mullinary Environmental Services Ltd NW CPO Reference: NW CPO-13-11213-02 Vehicle Registration Number: LoW Codes: 13 05 07* HP Codes: Comments: W aste Description: Interceptor Physical Characteristics: Sludgy, Liquid Special Handling Requirements: Wear PPE and Gloves RECEIVED: 12/11/2025 Waste Generator Details Waste Generator: Waste Generator Address: Waste Generator Registration Number: Household/non-waste facility: Mullinary Environmental Services Ltd T/A JC Environmental c/o Sragh Dismantlers Ltd, Ballybay, Co. Monaghan Consignee Details Consignee Name: Rilta Environmental Limited (W0192-03) Consignee Address: Block 402, Grant Drive, Greenogue Business Park, Rathcoole, Co Dublin Consignee Registration Number: W0192-03 Date Received: Tonnes Received: 0.00 Volume Received (m3): 0.00 LoW Codes: Comments on LoW Codes Differences: Comments: Trailer/Container Number Received: D Codes: R Codes: Notifier Signature Consignee Signature RECEIVED: 12/11/2025 RECEIVED: 12/11/2025 RECEIVED: 12/11/2025 RECEIVED: 12/11/2025 Butler Manufacturing Services Ltd Strokestown Rd Longford Ireland Tel:00 353 43 26100 / 26018 Fax:00 353 43 26258 Email:butler@iol.ie www.waste-watertreatment.com BMS Petrol/Oil Interceptors Petrol/Oil Interceptors Dara Creative Communications 1850 693 693All BMS products are manufactured under the ISO: 9001:2000 ‘A New Dimension’’ www.waste-watertreatment.com RECEIVED: 12/11/2025 CONCRETE SURROUND CONCRETE BASE WITH SUITABLE REINFORCEMENT AS DUG OR GRANULAR MATERIAL Concrete suitably reinforced in areas of vehicular traffic CONCRETE SURROUND SEPERATED BY SHUTTERING TO PREVENT LOAD TRANSFER BMS Petrol/Oil Interceptors BMS Petrol/Oil Interceptors For almost two decades BMS have provided the Forecourt, Construction and Industrial sectors with a quality range of proven products. In line with their ongoing Research and Development programmes, BMS are pleased to introduce an entirely new range of Interceptors designed to suit all applications. All products are manufactured to IS EN ISO: 9001:2000 and conform to European Standard PR EN 858 - 1 & 2 BMS Three Chamber Full Retention Interceptors BMS Three Chamber Full Retention Interceptors are available in a wide range of sizes varying from 1,100 Lts capacity up to 60,000 Lts. Larger sizes can be accommodated on order. Full Retention Interceptors are used in areas where there is a high risk of petrol/oil contaminating the drainage from site such as Fuel Distribution Depots, Scrap Yards, Car/ Vehicle Workshops and Washdown areas. BMS By Pass Interceptors Class 1 Used in low risk areas such as car parks and roadways where there is a risk of frequent oil contamination of surface water run off. BMS By Pass Interceptors Class 2 Used in applications where there is unlikely to be frequent oil contamination but potential risk of large spillage from an oil storage area. BMS Filterceptors Class 1 Doubles both as an Interceptor and Separator of pollutants on the petrol forecourt where there is significant risk of petrol/oil spillage. Designed to contain the maximum contents of a spillage from a fuel tanker compartment. Design, Construction, Quality New Designs have resulted in easier handling and better quality products. All interceptors are manufactured in Glass Reinforced Polyester ensuring that they are robust and rot proof. Finished units are rigorously tested by our Quality Control Department prior to despatch. Detailed sizing, installation and maintenance instructions are available with each unit. BMS Interceptors Petrol/Oil InterceptorsRECEIVED: 12/11/2025 RECEIVED: 12/11/2025 RECEIVED: 12/11/2025 RECEIVED: 12/11/2025