A detailed survey was carried out on the existing waste water treatment system at
Kednaminsha, Inniskeen, Co. Monaghan. The overall volume of the existing septic tank was
found to be 3.51m3. The holding capacity of the tank was found to be 2.93m3 (sketch of existing
septic tank attached in Appendix A).
Based on the no. of bedrooms in the existing dwelling a design PE of 6 is required. The resultant
minimum capacity is therefore (150 x 6 + 2000) = 2900 litres = 2.90m3. The existing septic tank
capacity exceeds the current standards required.
The existing tank is a single chamber tank and it is recommended to install a concrete baffle wall
to create 2 chambers. This will allow the solids to settle and digest within the first chamber
while the liquid enters the second chamber and onto the percolation area for further treatment.
The existing tank shall be made water tight prior to the construction of the baffle wall. In
addition 'T— pieces' shall be included on the inlet and outlet pipes and the concrete lids and air
vents shall be replaced were necessary. An effluent screen on the outlet pipe is recommended.
The existing manhole covers shall also be replaced were deemed necessary.
(see attached photo's of the existing on -site system in Appendix B)
It is proposed to install a new percolation area with 108m of percolation trench length as per
Table 7.2 in the EPA CODE OF PRACTICE 2021. (see Appendix C)
The trench width should be 500mm wide and no individual trench length should be longer than
18m. The Percolation trenches shall be constructed as per Table 7.3 & Figure 7.3 in the EPA
CODE OF PRACTICE — (see Appendix D).
Refer to the site layout for the position of the new percolation area.
In addition, I can confirm that the septic tank was constructed and installed when the original
dwelling and garage were built in the late 1980s.
In my opinion the existing septic tank is operating satisfactorily and with the additional
recommendations as stated above the system will meet current standards.
It is further recommended that the existing septic tank is emptied by a licensed contractor every
12-18 months.
If you have any queries in relation to the above, please do not hesitate to contact me.
Yours Sincerely
Noel Mc Gahon (Building Surveyor.)
Appendix A — Sketch of existing septic tank.
t4 -)—t E7T
ZSM,\ ELOCi Mj4G[S
PL,9s TE# E .
O uC . L -LOS v F S
v r vEI\tf
U Tt T
25
A,—
SINGE CMABC/ rs-T�Ali� .
Appendix B of Photographs
■ Fig 1-5 Images of the existing septic tank on -site.
Fig I
Fig 2
Fig 3
Fig 4
Fig 5
Appendix C
Table 7.2: Minimum percolation trench length
Appendix D
Geoteotile Surface
GraveMembrane Percolation
Ground Level Ground Level Test Hole
Subsurface
,»:: „� „ „�
ercolation �����If:; ';�\c, �a>\�t\ . �a��,\\ ��\� \\\�\\ �,\a. �. . �•`�\\�,:
0 150mm
i4ho, • a' 85omm R�n�� Test Hole Proposed Invert
Percolation ° ° = IOOmm of Percolation Pipe 300mm
Pipe $oae'�a -----
300mm
Water
o`. ba level I4o0mm
Base of the ;�q d¢4 fii.-----------
Percolation Trench a 5oomm _ t 100mm
30omm
1,200mm or 2,000mm minimum
Unsaturated above water table and/or bedrock
Undisturbed depending on the groundwater
Subsoil protection response (see Table 6.3)
Figure 7.3: Section of a typical percolation trench following a conventional septic tank
Table 7.3: Requirements of a percolation trench (gravity fed)
Slope of pipe from tank to
1 in 40 for earthenware or concrete,
distribution device
1 in 60 for uPVC
Slope of percolation trench from
1 in 200
distribution device
Length of percolation pipe in each
18 m maximum
trench
Minimum separation distance
2 m (2.5 m centre to centre)
between percolation trenches
Diameter of pipe from septic tank
100-110 mm
to distribution device
Percolation pipes'
100 mm bore, perforated (typically at 4, 6 and
8 o'clock) smooth wall PVC drainage pipes with
perforations of 8 mm diameter at about 75 mm
centres along the pipe or pipes with similar
hydraulic properties.
Maximum of six pipes per distribution device
Width of percolation trench
500 mm
Depth of percolation trench
Ideally, about 850mm° below ground surface
depending on site (as per Figures 7.1 and 7.3)
Depth of unsaturated soil and/or
Minimum 1.2 m for GWPRs of R1 or R2'. Minimum.
subsoil beneath percolation trench
2.0 m for GWPRs of R2?, R23, R2°, R3' or R32
and above the bedrock and the
water table
Backfilling of percolation trench
300 mm of 12-32 mm washed gravel or broken
(see Figure 7.1)
stone aggregate on invert; pipe laid at a 1 in 200
slope surrounded by 12-32 mm clean washed
gravel or broken stone aggregate and with 150
mm of similar aggregate over pipe; geotextile layer
followed by topsoil to ground surface
Geotextile
Geotextile should be in accordance with EN ISO
10319
Access/inspection points and vents
These are recommended for the ends of the
percolation pipes. The covers should be visible and
installed to prevent entry of water. They may also
be used for rodding or scouring purposes
a Before installation the holes in the percolation pipe should be inspected to check that
they are the correct size and free from debris.
b The percolation pipes may be located at a shallower depth, provided that a minimum,
of 450 mm of material is placed above the pipes to provide the required protection
against damage from above.