18/06/2026
Planning Section,
Monaghan County Council,
The Glen,
Monaghan
Planning App. Ref. No. 26/60177
Applicant Macartan View Limited
Retention Permission is sought for the following works:
•Works for plot units 24-27 inclusive to include for retention
of works to subfloor level as constructed. Permission is sought
for the following works: •A revised unit mix for units 1-27 to
provide for a total of 8 no. 2bed and 19 no. 3bed dwellings
(change of house types from units as granted); •Associated
reconfiguration of curtilage works associated with units 1-27
inclusive; •Amendments to façade and design of units 1-27;
No objections to the Planning Application subject to the following conditions:
1. The proposed building works shall comply with the requirements of the Building Control
Regulations (As Amended). Commencement Notice to be submitted via BCMS.
2. The design and construction of each dwelling shall comply with current Building Regulations
and specifically Technical Guidance Document Vol 2 Part B 2017 of the Building Regulations
with particular attention to the means of escape, separating wall detail between dwellings,
and provision of cavity barriers.
3. All siteworks shall be completed in accordance with the recommendations set out in DoECLG
publication “Recommendation for Site Development Works” including the provision of Fire
Hydrants to ensure that no dwelling is located more than 46.0m from a Fire Hydrant.
4. Fire Hydrants shall be in accordance with BS 750:2012 and shall deliver a minimum rate of
flow as per Monaghan Fire & Civil Protection ‘Guidance document for fire-fighting water
supplies’.
5. Fire Brigade Vehicle access to the proposed development shall be provided in accordance
with Clause 5.4 including Table 5.3 of Technical Guidance Document Part B 2017 Fire Safety -
Volume 2 Dwelling Houses including provision of turning facilities for appliances in dead-end
access routes more than 20.0m long.
6. The proposed development shall be designed and constructed in accordance with Technical
Guidance Document Part M 2010 (Access & Use) of the Second Schedule of the Building
Regulations, 1997-2022.
Regards,
Dermot Brannigan
Chief Fire Officer