HomeMy WebLinkAbout2660348 - Drawings - General - Poultry Unit DrawingSide Elevation
1:200
Side Elevation
1:200
'X'
'X'
Plan View
1:200
Broiler Floor Area 2,650.0m² (28,525.0Ft.²)
Stocking Capacity :- 50,000.00 Broilers
APEX HAUNCHES SHALL BE CUT OUT OF SAME SECTION AS THE
RAFTERS. HAUNCHES SHALL BE WELDED TO RAFTER FLANGE
WITH DOUBLE FILLET WELD FOR FULL LENGTH OF HAUNCH; 15MM
END PLATES SHALL BE WELDED TO THE END OF EACH
RAFTER/HAUNCH CONNECTION WITH A DOUBLE FILLET WELD FOR
FULL DEPTH OF RAFTER/HAUNCH COMBINATION. CONNECTION
PLATES TO BE JOINTED WITH 6 NR. 20 MM BOLTS (8.8 GRADE)
EVENLY SPACED.
KNEE HAUNCHES SHALL BE CUT OUT OF THE SAME SECTION
AS THE RAFTERS, TO A MIN. 1830MM LENGTH . HAUNCHES
SHALL BE WELDED TO THE RAFTER FLANGE WITH DOUBLE
FILLET WELD FOR FULL LENGTH OF HAUNCHES; 15MM END
PLATES SHALL BE WELDED TO STANCHION END OF
RAFTER/HAUNCH COMBINATION, . 10 NR 20MM (8.8 GRADE)
BOLTS TO BE PROVIDED AT THE 'KNEE BRACE' AT THE
EAVES & BE EVENLY SPACED. WEB STIFFENERS OF 12MM
STEEL PLATE SHALL BE INSERTED INTO THE STANCHION AT
BOTTOM OF HAUNCH AND A SIMILAR STIFFENER INTO THE
RAFTER, AT TOP END OF HAUNCH.
FOUNDATIONS
THE CONCRETE FOUNDATION PIERS SHALL BE 900 X 900MM THAT IS CARRIED UP FROM
SOLID STRATA, AND BE AT LEAST 900MM DEEP.
THE STANCHIONS SHALL BE INSERTED INTO THE PIERS A MINIMUM DEPTH OF 600MM OR
ALTERNATIVELY, SHALL BE SECURED TO THE PIERS IN AN APPROVED MANNER USING STEEL
BASE PLATES (MIN. THICKNESS 12MM) WELDED TO THE BASE OF THE STANCHION, AND
HOLDING DOWN BOLTS. CORNER STANCHIONS SHALL BE BOLTED DOWN WITH 4 NO. 20MM
HOLDING DOWN BOLTS, 450MM LONG. BOLTS HOLES IN BASE PLATE TO BE A MINIMUM OF
40MM IN FROM EITHER EDGE OF PLATE. BASE PLATES FOR INTERMEDIATE STANCHIONS
SHALL BE BOLTED DOWN WITH 2 NO. 20MM HOLDING DOWN BOLTS, 450MM LONG. BOLT
HOLES IN PLATE TO BE A MINIMUM OF 40MM FROM EDGE OF PLATE AND SET AT CENTRE OF
STANCHION WEB .
HOLDING DOWN BOLTS SHALL BE SECURED INTO FOUNDATION PIER BY USING 75MM X 75MM
STEEL ANGLE WHICH IS DRILLED TO ACCOMMODATE THE BOLTS. THE BOLTS ARE THEN
THREADED THROUGH AND FIXED SECURELY IN FOUNDATION PAD BEFORE POURING
CONCRETE. A SUITABLE TEMPLATE SHALL BE USED, TO KEEP BOLTS IN CORRECT POSITION
FOR BASE PLATES DURING POURING CONCRETE (FIGURE 26).
WHERE STANCHIONS ARE OFFSET IN FOUNDATION BLOCKS, REINFORCEMENT SHALL BE USED
IN THE FOUNDATION.
NOTE: PATENT ANCHOR BOLTS MAY BE ALLOWED IN PLACE OF CAST-IN BOLTS, PROVIDED
THEY ARE SIZED, AND INSTALLED, IN STRICT ACCORDANCE WITH THE MANUFACTURER'S
SPECIFICATIONS AND INSTRUCTIONS.
CONCRETE FLOORS
SOLID FLOORS SHALL BE A MINIMUM 125MM 35N CONCRETE LAID SMOOTH
WITH A NON-SLIP FINISH & REINFORCED WITH A142 MESH TO PREVENT
CRACKING. [CUT JOINTS TO BE INTRODUCED AT SUITABLE CENTRES] . A
MINIMUM 150MM HARD-CORE BASE SHALL BE LAID, COMPACTED WITH
VIBRATING OR HEAVY ROLLER, AND TOPPED WITH FINE SAND. ALL
FLOORS SHALL INCORPORATE 1000 GAUGE POLYTHENE DPC MEMBRANE
WITH 600MM OVERLAPS LAID ON THE SAND UNDER CONCRETE. THE
POLYTHENE MEMBRANE SHALL BE TAKEN UP ALONG WALLS TO MEET
DPC WHERE THIS HAS BEEN INSTALLED.
Section On 'X-X'
1:100
Front Elevation
1:200
Rear Elevation
1:200
B7 CONCRETE FOUNDATIONS
B7.1 Foundation Piers for Stanchions: Stanchions shall be carried on, or built
into a concrete pier minimum 600 x 600mm that is carried up from solid strata, and is
at least 600mm deep. For structures with spans greater than 12m and in all portal
frames, the concrete foundation pier shall be 900 x 900mm that is carried up from
solid strata, and be at least 900mm deep.
Note: For stanchions erected, or portal frames carried, on tank walls, see Clause
4.7, S123.
The stanchions shall be inserted into the piers a minimum depth of 600mm or
alternatively, shall be secured to the piers in an approved manner using steel base
plates (min. thickness 12mm) welded to the base of the stanchion, and holding down
bolts. Corner stanchions shall be bolted down with 4 No. 20mm holding down bolts,
450mm long. Bolts holes in base plate to be a minimum of 40mm in from either edge
of plate. Base plates for intermediate stanchions shall be bolted down with 2 No.
20mm holding down bolts, 450mm long. Bolt holes in plate to be a minimum of
40mm from edge of plate and set at centre of stanchion web (Figure 26).
Holding down bolts shall be secured into foundation pier by using 75mm x 75mm
steel angle which is drilled to accommodate the bolts. The bolts are then threaded
through and fixed securely in foundation pad before pouring concrete. A suitable
template shall be used, to keep bolts in correct position for base plates during pouring
concrete (Figure 26).
Where stanchions are offset in foundation blocks, reinforcement shall be used in the
foundation.
Note: Patent anchor bolts may be allowed in place of cast-in bolts, provided they are
sized, and installed, in strict accordance with the manufacturer's specifications and
instructions.
B8 CONCRETE FLOORS
Solid Floors shall be a minimum 125mm concrete laid smooth with a non-slip finish.
Concrete shall comply with Clause B6 above. A minimum 150mm hard-core base
shall be laid, compacted with vibrating or heavy roller, and topped with fine sand. All
floors shall incorporate 1000 gauge polythene DPC membrane with 600mm overlaps
laid on the sand under concrete. The polythene membrane shall be taken up along
walls to meet DPC where this has been installed.
B9 MASS CONCRETE / BLOCKWORK WALLS
Note:
·Walls are not mandatory for bovine houses other than calf/suckler houses (see
Specification S.123), or for sheep houses. Barriers may be used instead. (Evidence
suggests that animals may be healthier in such houses.) When installed, wall
heights for animal houses are to be chosen to allow the appropriate ventilation
above them (clause B2). Such walls will normally not exceed 1.5m in height.
·For walls erected on tank walls, refer to Specification S123.
B9.1 Non Load-bearing superstructure walls Where stanchions are at 4.8m
spacing or less, the infill wall shall be a minimum of 150mm thick. Where stanchions are
spaced between 4.8m and 6.4m, then the wall thickness shall be at least 200mm.
B9.2 Proprietary precast concrete wall panels shall require prior Departmental
acceptance, and may be subject to requirements for certificates of guarantee.
B9.3 Mass concrete walls Mass concrete in-fill walls shall be constructed with
nominal mesh reinforcement. (Minimum mesh A98: 5mm at 200mm x 200mm;
1.54kg/m2). Mesh shall be placed on outside face of wall with 40mm concrete cover. It
is strongly recommended that gable walls should be in mass concrete. Any blemishes,
tie-bar holes, or honeycombing in mass concrete walls shall be filled/repaired with an
accepted, non-shrink proprietary cement mortar.
B9.4 Tying-in walls to stanchions In-fill walls shall be built into and secured to the
web of the stanchion. Where walls abut the flange of the stanchion an angle section shall
be welded to both edges of the flange to form a recess for the wall. These angle sections
shall extend from 450mm above wall foundation to the top of wall. To minimise
corrosion a continuous weld shall be used. The weld shall be protected with a coating to
clause B3. Alternatively, they shall be secured to the flange with 10mm steel dowels,
225mm long at a maximum vertical spacing of 450mm.
B9.5 In gables, stanchions to support the gable walls shall be erected from the
foundation and be secured to the steel rafter or to a steel cross beam at approximately
wall height. For 150mm walls, spacing of these stanchions shall be 5m maximum, and
for 200mm walls the maximum spacing shall be 7m. Stanchions shall also be positioned
at openings for central passage doors.
B9.6 All block walls in animal houses, dairies and milking premises shall be
rendered internally with two coats, 12mm and 6mm respectively, with 3:1 sand cement
rendering with plasticiser or ¼ part lime, to a smooth steel trowel finish. Block walls
shall be rendered externally with one coat 12mm thick to a nap or smooth finish.
B10 ROOF CLADDING & SIDE CLADDING
BB12 ROOF DRAINAGE
Gutters and Down Pipes shall be fitted complete with necessary brackets and
securely fixed. The number of bays drained by a standard 150mm half-round gutter is
as follows:-
Up-slope length of roof not exceeding 6.0m 8.5m 10m12mNo. of 4.8m bays drained
by gutter with a min. slope of 10mm/bay . A 75mm down-pipe is adequate for any of
the above combinations, if situated at one end of the gutter run; otherwise a 100mm
down-pipe is required. Down-pipes shall be protected against damage. Pipes shall
discharge at ground level over a gully trap or preferably through a back inlet type
gully trap, to the clean water disposal system. All drainage shall comply with
specification S129:- Farmyard Drainage.
B15 DOORS
All doors wider than 1.2m shall be sliding. Doors to central passages, where fitted,
shall also be sliding. The sliding gear shall be fitted and erected as per manufacturers
instructions for the size and weight of door fitted. A sliding door should preferably
incorporate a hinged type outward-opening single personnel door with a minimum
head-height of 2.2m above ground level. Cladding materials for doors shall conform,
at least, to the standards specified in S102. Steel roller doors are also permitted.
En
c
o
r
e
C
o
n
s
u
l
t
i
n
g
KEVIN MC VICAR
Mullaliss
Glaslough
Co Monaghan
Project:
Drawing Title:
Drawing: ENPL2026 - 08 - 01
Date: 25.02.2026
Scale As Shown
Rev:
Drawn By: JB
Joe Beggan
Encore Consulting
087 - 2924047
email :- jgbeggan@gmail.com
Rev Date Amendment
Poultry Unit Drawing
Proposed New Broiler House